109AGPS-11CNominal input voltage 115...230 V AC ±10%Nominal input curr<strong>en</strong>t 0.1 A (230 V) / 0.2 A (115 V)Nominal frequ<strong>en</strong>cy50/60 HzMax. external fuse16 AX1 terminal sizes 3 x 2.5 mm 2Output voltage15 V DC ±0.5 VNominal output curr<strong>en</strong>t 0.4 AX2 terminal block type JST B4P-VHAmbi<strong>en</strong>t temperature 0...50 °CRelative humidityMax. 90%, no cond<strong>en</strong>sation allowedDim<strong>en</strong>sions (with <strong>en</strong>closure) 167 x 128 x 52 mm (Height x Width x Depth)Weight (with <strong>en</strong>closure) 0.75 kgApprovalsC-UL, US listedAmbi<strong>en</strong>t conditionsInstallation site altitudeAir temperatureEnvironm<strong>en</strong>tal limits for the drive are giv<strong>en</strong> below. The drive is to be used in a heated,indoor, controlled <strong>en</strong>vironm<strong>en</strong>t.Operationinstalled for stationary use0 to 4000 m (13123 ft) abovesea level [above 1000 m(3281 ft), see sectionDerating]-15 to +50 °C (5 to 122 °F).No frost allowed. See sectionDerating.Storagein the protective package- --40 to +70 °C (-40 to+158 °F)Transportationin the protective package-40 to +70 °C (-40 to+158 °F)Relative humidity 5 to 95% Max. 95% Max. 95%No cond<strong>en</strong>sation allowed. Maximum allowed relative humidity is 60% in the pres<strong>en</strong>ce ofcorrosive gases.Contamination levels(IEC 60721-3-3, IEC 60721-3-2, IEC 60721-3-1)Atmospheric pressureVibration (IEC 60068-2)*No conductive dust allowed.Boards without coating:Chemical gases: Class 3C1Solid particles: Class 3S2Boards with coating:Chemical gases: Class 3C2Solid particles: Class 3S270 to 106 kPa0.7 to 1.05 atmospheresMax. 1 mm (0.<strong>04</strong> in.)(5 to 13.2 Hz),max. 7 m/s 2 (23 ft/s 2 )(13.2 to 100 Hz) sinusoidalBoards without coating:Chemical gases: Class 1C2Solid particles: Class 1S3Boards with coating:Chemical gases: Class 1C2Solid particles: Class 1S370 to 106 kPa0.7 to 1.05 atmospheresMax. 1 mm (0.<strong>04</strong> in.)(5 to 13.2 Hz),max. 7 m/s 2 (23 ft/s 2 )(13.2 to 100 Hz) sinusoidalShock (IEC 60068-2-29) Not allowed Max. 100 m/s 2 (330 ft./s 2 ),11 msFree fall Not allowed 250 mm (10 in.) for weightunder 100 kg (220 lb)100 mm (4 in.) for weightover 100 kg (220 lb)Boards without coating:Chemical gases: Class 2C2Solid particles: Class 2S2Boards with coating:Chemical gases: Class 2C2Solid particles: Class 2S260 to 106 kPa0.6 to 1.05 atmospheresMax. 3.5 mm (0.14 in.)(2 to 9 Hz),max. 15 m/s 2 (49 ft/s 2 )(9 to 200 Hz) sinusoidalMax. 100 m/s 2 (330 ft./s 2 ),11 ms250 mm (10 in.) for weightunder 100 kg (220 lb)100 mm (4 in.) for weightover 100 kg (220 lb)*Note: For frame sizes R2 to R4 with panel option maximum allowed vibration is 3 m/s 2 . For higher vibration use theRPMP kit. See Control Panel Mounting Platform Kit (RPMP) Installation Guide [3AFE64677560 (English)].Technical data