46Note 7: Calculating the rise time and the peak line-to-line voltageThe peak line-to-line voltage at the motor terminals g<strong>en</strong>erated by the drive as well as the voltage risetime dep<strong>en</strong>d on the cable l<strong>en</strong>gth. The requirem<strong>en</strong>ts for the motor insulation system giv<strong>en</strong> in the tableare “worst case” requirem<strong>en</strong>ts covering installations with 30 metre and longer cables. The rise time canbe calculated as follows: t = 0.8 · Û LL /(du/dt). Read Û LL and du/dt from the diagrams below. Multiplythe values of the graph by the supply voltage (U N ).With resistor braking, the Û LL and du/dt values areapproximately 20 % higher.3.02.5Û LL /U N5.55.<strong>04</strong>.5du/dt------------(1/μs)U N2.<strong>04</strong>.01.51.00.5du/dt------------(1/μs)U N3.53.02.52.01.5Û LL /U N0.0100 200 3001.0100 200 300Cable l<strong>en</strong>gth (m)Cable l<strong>en</strong>gth (m)With du/dt filterWithout du/dt filterNote 8: Sine filters protect the motor insulation system. Therefore, du/dt filter can be replaced witha sine filter. The peak phase-to-phase voltage with the sine filter is approximately 1.5 × U N .Note 9: Common mode filter is available as a separate kit (one box including three rings for one cable).Perman<strong>en</strong>t magnet synchronous motorSupply connectionOnly one perman<strong>en</strong>t magnet motor can be connected to the inverter output.It is recomm<strong>en</strong>ded to install a safety switch betwe<strong>en</strong> the perman<strong>en</strong>t magnetsynchronous motor and the drive output. The switch is needed to isolate the motorduring any maint<strong>en</strong>ance work on the drive.Disconnecting device (means)Install a hand-operated input disconnecting device (disconnecting means) betwe<strong>en</strong>the AC power source and the drive. The disconnecting device must be of a type thatcan be locked to the op<strong>en</strong> position for installation and maint<strong>en</strong>ance work.Planning the electrical installation

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!