51Selecting the power cablesG<strong>en</strong>eral rulesDim<strong>en</strong>sion the mains (input power) and motor cables according to localregulations:• The cable must be able to carry the drive load curr<strong>en</strong>t. See chapter Technicaldata for the rated curr<strong>en</strong>ts.• The cable must be rated for at least 70 °C maximum permissible temperature ofconductor in continuous use. For US, see section Additional US requirem<strong>en</strong>ts.• The inductance and impedance of the PE conductor/cable (grounding wire) mustbe rated according to permissible touch voltage appearing under fault conditions(so that the fault point voltage will not rise excessively wh<strong>en</strong> a ground faultoccurs).• 600 V AC cable is accepted for up to 500 V AC. 750 V AC cable is accepted forup to 600 V AC. For 690 V AC rated equipm<strong>en</strong>t, the rated voltage betwe<strong>en</strong> theconductors of the cable should be minimum 1 kV.For drive frame size R5 and larger, or motors larger than 30 kW (40 HP),symmetrical shielded motor cable must be used (figure below). A four-conductorsystem can be used up to frame size R4 with up to 30 kW (40 HP) motors, butshielded symmetrical motor cable is always recomm<strong>en</strong>ded. The shield(s) of motorcable(s) must have 360° bonding at both <strong>en</strong>ds.Note: Wh<strong>en</strong> continuous metal conduit is employed, shielded cable is not required.The conduit must have bonding at both <strong>en</strong>ds as with cable shield.A four-conductor system is allowed for input cabling, but shielded symmetrical cableis recomm<strong>en</strong>ded. To operate as a protective conductor, the shield conductivity mustbe as follows wh<strong>en</strong> the protective conductor is made of the same metal as the phaseconductors:Cross-sectional area of the phaseconductorsS (mm 2 )S < 16Minimum cross-sectional area of the correspondingprotective conductorS p (mm 2 )S16 < S < 35 1635 < S S/2Compared to a four-conductor system, the use of symmetrical shielded cablereduces electromagnetic emission of the whole drive system as well as the stress onmotor insulation, bearing curr<strong>en</strong>ts and wear.The motor cable and its PE pigtail (twisted shield) should be kept as short aspossible in order to reduce high frequ<strong>en</strong>cy electromagnetic emission, as well asstray curr<strong>en</strong>ts outside the cable and capacitive curr<strong>en</strong>t (relevant in power rangebelow 20 kW).Planning the electrical installation

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!