74Prev<strong>en</strong>tion of Unexpected Start, AGPS boardWARNING! Dangerous voltages can be pres<strong>en</strong>t on the AGPS board ev<strong>en</strong> wh<strong>en</strong> the115...230 V supply is switched off. Follow the Safety instructions on the first pages ofthis manual and the instruction in this section wh<strong>en</strong> working on the AGPS board.Make sure that the drive is disconnected from the mains (input power) and the115...230 V source for the AGPS board is switched off during installation andmaint<strong>en</strong>ance. If the drive is already connected to the mains, wait for 5 min afterdisconnecting mains power.Connect the optional AGPS board as follows:• Remove the <strong>en</strong>closure cover by undoing the fixing screws (1).• Ground the unit via the bottom plate of the <strong>en</strong>closure or via terminal X1:1 of theAGPS board.• Connect the cable delivered with the kit betwe<strong>en</strong> terminal block X2 of the AGPSboard (2) and drive terminal block X41.• Connect a cable betwe<strong>en</strong> connector X1 of the AGPS board (3) and the115...230 V source.• Fast<strong>en</strong> the <strong>en</strong>closure cover back with screws.12X2X1115...230 V3Electrical installation