86FanThe cooling fan lifespan of the drive is about 50 000 operating hours. The actuallifespan dep<strong>en</strong>ds on the drive usage and ambi<strong>en</strong>t temperature. See the appropriate<strong>ACS800</strong> Firmware Manual for an actual signal which indicates the hours of usage ofthe fan. For resetting the running time signal after a fan replacem<strong>en</strong>t, please contactABB.Fan failure can be predicted by the increasing noise from fan bearings and thegradual rise in the heatsink temperature in spite of heatsink cleaning. If the drive isoperated in a critical part of a process, fan replacem<strong>en</strong>t is recomm<strong>en</strong>ded once thesesymptoms start appearing. Replacem<strong>en</strong>t fans are available from ABB. Do not useother than ABB specified spare parts.Fan replacem<strong>en</strong>t (R2, R3)To remove the fan, release the retaining clips. Disconnect the cable. Install the newfan in reverse order.Bottom viewMaint<strong>en</strong>ance