44ManufacturerNON-ABBMotor typeRandomwoundandform-woundNominal mainsvoltage (AC linevoltage)MotorinsulationsystemU N < 420 V Standard: Û LL =1300 V420 V < U N < 500 V Standard: Û LL =1300 VorReinforced:Û LL = 1600 V,0.2microsecondrise time500 V < U N < 600 V Reinforced: Û LL= 1600 VorReinforced:Û LL = 1800 V600 V < U N < 690 V Reinforced:Û LL = 1800 VReinforced:Û LL = 2000 V,0.3microsecondrise time ***Requirem<strong>en</strong>t forABB du/dt filter, insulated N-<strong>en</strong>d bearing and ABB commonmode filterP N < 100 kWandframe size < IEC315P N < 134 HPand frame size 350 kWorframe size > IEC400P N > 469 HPor frame size >NEMA 580* manufactured before 1.1.1998** For motors manufactured before 1.1.1998, check for additional instructions with the motormanufacturer.*** If the intermediate DC circuit voltage of the drive will be increased from the nominal level by resistorbraking or by the IGBT Supply Control Program (parameter selectable function), check with themotor manufacturer if additional output filters are needed in the applied drive operation range.Planning the electrical installation