70Cabling of I/O and fieldbus modulesAs short as possibleModuleShield1234Note: The RDIO module does notinclude a terminal for cable shieldgrounding. Ground the pair cableshields here.Pulse <strong>en</strong>coder module cabling1234ShieldAs short aspossibleRTACNote1: If the <strong>en</strong>coder is ofunisolated type, ground the <strong>en</strong>codercable at the drive <strong>en</strong>d only. If the<strong>en</strong>coder is galvanically isolatedfrom the motor shaft and the statorframe, ground the <strong>en</strong>coder cableshield at the drive and the <strong>en</strong>coder<strong>en</strong>d.Note 2: Twist the pair cable wires.Wrap copper tape around thestripped part of the cable under theclamp. Be careful. Do not cut thegrounding wire. Clamp as close tothe terminals as possible.Electrical installation