52Alternative power cable typesPower cable types that can be used with the drive are repres<strong>en</strong>ted below.Recomm<strong>en</strong>dedSymmetrical shielded cable: three phase conductorsand a conc<strong>en</strong>tric or otherwise symmetricallyconstructed PE conductor, and a shieldA separate PE conductor is required if the conductivityof the cable shield is < 50% of the conductivity of thephase conductor.PE conductorand shieldShieldShieldPEPEA four-conductor system:three phase conductorsand a protectiveconductor.PENot allowed for motor cablesShieldNot allowed for motor cables with phaseconductor cross section larger than 10 mm 2[motors > 30 kW (40 HP)].Motor cable shieldTo effectively suppress radiated and conducted radio-frequ<strong>en</strong>cy emissions, theshield conductivity must be at least 1/10 of the phase conductor conductivity. Therequirem<strong>en</strong>ts are easily met with a copper or aluminium shield. The minimumrequirem<strong>en</strong>t of the motor cable shield of the drive is shown below. It consists of aconc<strong>en</strong>tric layer of copper wires with an op<strong>en</strong> helix of copper tape or copper wire.The better and tighter the shield, the lower the emission level and the bearingcurr<strong>en</strong>ts.Insulation jacketCopper wire scre<strong>en</strong>Helix of copper tapeor copper wireInner insulationCable corePlanning the electrical installation

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!