Net F/T Installation and Operation Manual<br />
Document: 9620-05-net ft-11<br />
Table 16.3—Output Mapping<br />
Byte Bit Name Description/Function<br />
0<br />
1<br />
0 Bias Perform tare function to zero out any load reading<br />
1 Reset Latch Reset threshold latch<br />
2 reserved<br />
3 reserved<br />
4 reserved<br />
5 reserved<br />
6 reserved<br />
7 reserved<br />
0 Config Select bit 0<br />
1 Config Select bit 1<br />
2 Config Select bit 2<br />
3 Config Select bit 3<br />
4 reserved<br />
Selects a Net F/T configuration, from 0 to 15<br />
5 reserved<br />
6 reserved<br />
7 reserved<br />
2 0-7 Threshold high Threshold enable mask, high byte<br />
3 0-7 Threshold low Threshold enable mask, low byte<br />
Output byte 0, bit 0 performs a bias function when it is set to one. See the bias button<br />
information in Section 4.3—Snapshot Page (rundata.htm) for details on this function. Bit 0<br />
should be set to one for at least 100ms to ensure the bias is executed. Then it should be<br />
returned to zero.<br />
Output byte 0, bit 1 performs a reset threshold latch function when it is set to one. See the reset<br />
latch button information in Section 4.6—Thresholding Page (moncon.htm) for details on this<br />
function. Bit 1 should be set to one for at least 100ms to ensure a reset latch is executed. Then<br />
it should be returned to zero.<br />
Output byte 0, bits 2–7 are reserved and should not be used.<br />
Output byte 1, bits 0–3 select the active configuration (0 through 15) to be used. There is a<br />
delay of up to one second before the newly-selected configuration becomes usable. During the<br />
change of configuration s, the Net F/T does not supply valid force and torque data. See the<br />
active configuration information in Section 4.5—Settings Page (setting.htm) for details on<br />
active configuration.<br />
Output byte 1, bits 4–7 are reserved and should not be used.<br />
Output bytes 2 and 3 form a 16-bit threshold enable mask that enables and disables threshold<br />
conditions. Each bit, 0–15, of the threshold enable mask maps directly to its corresponding<br />
threshold condition number N. A value of one enables the corresponding condition while a<br />
value of zero disables the condition. See Section 4.6—Thresholding Page (moncon.htm) for<br />
more information on thresholding.<br />
NOTICE: When Fieldbus Module Enabled is set to Enabled (on the<br />
Communications Settings page), active configuration selection and thresholding<br />
statement selection is controlled by the PROFINET output data. While enabled,<br />
these values are not controlled by Net Box web pages or CGI interface.<br />