4. Verify the tank position. The Connected to HUB field shows the name of<br />

the 2410 Tank Hub and the tank position that the 5400 is mapped to in<br />

the 2410 tank database. The tank position indicates which tank the 5400<br />

is associated with.<br />

In case the 5400 transmitter is connected to a multiple tank version of the<br />

Rosemount 2410, the 5400 may be mapped to another tank position via<br />

the 2410 Tank Hub Properties/Tank Database window if needed (in the<br />

WinSetup workspace, click the right mouse button on the 2410 icon and<br />

choose the Properties option).<br />

See “Tank Database Setup” on page 5-42 for more information on how to<br />

configure the 2410 Tank Database.<br />

5. Verify that the Modbus address is correct. To change the Modbus<br />

address click the Change button:<br />

a. Enter the Unit ID in the Unit ID input field.<br />

When changing the device address, the Unit Id is used as a unique<br />

identifier of the device. The Unit Id can be found on a label mounted<br />

on the device.<br />

b. Set the desired address in the Set Modbus Address input field.<br />

c. Click the OK button to confirm the settings and to close the Change<br />

Address window.<br />

6. Click the Apply button to store the configuration, or click the OK button<br />

to store the configuration and close the window.<br />

5-80 Section 5. Installing a Raptor Level Gauging System