System Configuration Manual<br />

300510EN, Rev AA<br />

December 2010<br />

Rosemount Raptor<br />

The following antenna types are available:<br />

5900S with Horn Antenna<br />

• Horn<br />

5900S with Parabolic Antenna<br />

• Parabolic<br />

5900S with Still-pipe Array Antenna<br />

• Still-Pipe Array Fixed<br />

• Still-Pipe Array Hatch<br />

5900S with LPG Antenna<br />

Depending on the pressure rating of the flange, choose one of the following<br />

options:<br />

• LPG/LNG 150 PSI + Valve<br />

• LPG/LNG 150 PSI<br />

• LPG/LNG 300 PSI + Valve<br />

• LPG/LNG 300 PSI<br />

• LPG/LNG 600 PSI + Valve<br />

• LPG/LNG 600<br />

For Still-pipe Array antennas you need to specify Antenna Size and Pipe<br />

Diameter. The Pipe Diameter is used to compensate for the lower microwave<br />

propagation speed inside a still-pipe. See also “Using the Calibrate Function”<br />

on page 5-123 for information on how to calibrate the 5900S for still-pipe<br />

installations.<br />

To configure a User Defined antenna (advanced)<br />

The User Defined option (User Def. Free Propagation, User Def. Linear Pipe,<br />

and User Def. Modeconv. Pipe) should only be used in special situations for<br />

non-standard antennas:<br />

a. Choose the appropriate antenna type:<br />

- User Defined Free Propagation<br />

- User Defined Pipe<br />

- User Defined Pipe Array<br />

b. Enter the Tank Connection Length in the TCL input field.<br />

c. For still pipe applications, type the inner diameter of the still pipe in<br />

the Pipe Diameter input field.<br />

d. In case there are disturbances close to the nozzle you may need to<br />

adjust the Hold Off Distance. By increasing the Hold Off distance,<br />

the measurement range is reduced in the upper part of the tank.<br />

9. In the 5900S RLG Properties/Antenna window click the Apply button to<br />

save the configuration.<br />

See Rosemount 5900S Reference Manual (Document No. 300520EN)<br />

for more information on Hold Off Distance and other level gauge<br />

parameters.<br />