Rosemount Raptor<br />

7.3.1 User Defined<br />

Linearization<br />

Table<br />

When using a resistance temperature sensor, the electrical resistance values<br />

can be converted to temperature values by using a table of resistance and<br />

temperature values.<br />

To create a conversion table:<br />

1. In the 2240S MTT Temperature Sensor window, choose conversion<br />

method User Defined Linearization Table.<br />

2. Click the Configure User Defined Linearization Table button:<br />

3. Specify the number of conversion points in the Length of Table input<br />

field.<br />

4. Type resistance and temperatures values into the Resistance [Ohm]<br />

and Temperature [C] columns.<br />

5. Click the OK button to store the linearization table in the temperature<br />

transmitter’s database registers.<br />

Section 7. Service Functions<br />

7-5