Rosemount Raptor<br />

System Configuration Manual<br />

300510EN, Rev AA<br />

December 2010<br />

The 2410 Temp address in the 2160 FCU Slave Database must be equal to<br />

the ATD Modbus address in the 2410 Tank Database.<br />

For tank TK-1 the ATD Modbus address is entered in position 1B in the 2160<br />

FCU Slave Database and is automatically assigned to tank position 1 in the<br />

2410 Tank Database.<br />

The ATD Modbus address for tank TK-2 is entered in position 2B in the 2160<br />

FCU Slave Database and is automatically assigned to tank position 1 in the<br />

Tank Database of the second 2410 Tank Hub.<br />

Figure 5-5 illustrates how to configure the 2160 FCU and the two 2410 Tank<br />

Hubs for the ATD devices on tanks TK-1 and TK-2:<br />

Figure 5-5. The same Modbus<br />

address must be configured for<br />

the ATD devices in the 2410<br />

Tank Database and the 2410<br />

Temp devices in the 2160 Slave<br />

Database<br />

2410 TANK DATABASE: TK-1<br />

2160 FCU SLAVE DATABASE<br />

2410 TANK DATABASE: TK-2<br />

Note!<br />

For a tank at Tank Position 1<br />

the ATD Modbus address is<br />

equal to the Modbus address<br />

of the 2410 Tank Hub itself<br />

5-34 Section 5. Installing a Raptor Level Gauging System