System Configuration Manual<br />

300510EN, Rev AA<br />

December 2010<br />

Rosemount Raptor<br />

Tank Environment<br />

Certain tank conditions may require additional configuration of the 5900S<br />

Radar Level Gauge in order to optimize measurement performance. By<br />

considering environmental conditions in the tank, the 5900S can compensate<br />

for conditions such as rapid level change, weak echo signals, or varying<br />

surface echo amplitudes.<br />

To configure the 5900S Radar Level Gauge for special tank conditions:<br />

1. In the 5900S RLG Properties window select the Environment tab:<br />

2. Select the check boxes that correspond to the conditions in the tank.<br />

Use as few options as possible. It is recommended that no more than<br />

two options are used simultaneously.<br />

3. Choose the Product Dielectric Range from the drop-down list.<br />

Choose the Unknown option if the correct value range is unknown or if<br />

the contents of the tank is changing on a regular basis.<br />

4. Click the OK button to save the configuration and close the window.<br />

See the Rosemount 5900S Reference Manual (Document No. 300520EN) for<br />

more information on tank environment settings.<br />

Section 5. Installing a Raptor Level Gauging System<br />

5-63