Rosemount Raptor<br />

System Configuration Manual<br />

300510EN, Rev AA<br />

December 2010<br />

6. Configure the Group Bus (GB) and Field Bus (FB) ports on the FCU.<br />

a. Check that the correct port type is selected (1) . The Rosemount 2160<br />

has six communication ports. They are normally configured as two<br />

Group Bus ports and four Field Bus ports.<br />

Group Bus ports can be connected to TankMaster work stations as<br />

well as to other hosts.<br />

The Field Bus ports are connected to Rosemount 2410 Tank Hubs<br />

and level gauging devices.<br />

b. Ensure that the Modbus protocol is selected.<br />

c. Ensure that the following Modbus protocol communication<br />

parameters are used for the fieldbus that the Rosemount 2410 Tank<br />

Hub is connected to:<br />

Table 5-1. Modbus<br />

communication parameters for<br />

fieldbus communication with a<br />

Rosemount 2410 Tank Hub<br />

Parameter RS485 bus TRL2 bus<br />

Baud rate 9600 4800<br />

Databits per character 8 8<br />

Stop bits 1 1<br />

Parity No No<br />

See “Communication Protocol Setup” on page 5-6 for more<br />

information.<br />

d. The Redundancy button is not used for stand-alone FCU<br />

installations.<br />

e. Click the Next button to open the FCU Properties/Slave Database<br />

window.<br />

(1) As standard the 2160 FCU is equipped with FCM communication boards for the TRL2 bus.<br />

RS-485 communication requires a FCI board.<br />

5-28 Section 5. Installing a Raptor Level Gauging System