Rosemount Raptor<br />
System Configuration Manual<br />
300510EN, Rev AA<br />
December 2010<br />
5.1 SYSTEM CONFIGURATION OVERVIEW<br />
5.1.1 Preparations Before installing a Rosemount Tank Gauging system you should ensure that<br />
the following information is available:<br />
• A plan of all field devices and tanks.<br />
• Unit IDs of each device (Unit ID is a unique identifier given to each<br />
Raptor device at factory).<br />
• Modbus addresses of level devices and ATD devices. The Raptor<br />
devices are shipped with default addresses which will be changed at<br />
system configuration. The Modbus addresses are configured in the<br />
Slave Database of the 2160 FCU and the Tank Database of the 2410<br />
Tank Hub as described below.<br />
• Tank geometry parameters and reference distances such as tank<br />
reference height (R) and distance between Zero level (datum plate)<br />
and tank bottom.<br />
• Antenna types used for the various level gauges.<br />
5.1.2 Installation<br />
Procedure<br />
Installation and configuration of a Rosemount Raptor level gauging system<br />
includes the following steps as briefly described below:<br />
1 Communication Protocol Setup<br />
Specify communication protocol parameters:<br />
• The Modbus Master Protocol handles communication between a<br />
TankMaster work station and field devices such as the Rosemount<br />
2160 Field Communication Unit and the Rosemount 2410 Tank Hub.<br />
• The Slave Protocol handles communication with a host computer.<br />
• Communication with TankMaster can be supervised by logging various<br />
error types and function codes.<br />
2 Preferences<br />
Specify measurement units, tag prefixes for tank and device labels,<br />
inventory parameters, and parameters to be displayed when viewing tank<br />
data.<br />
3 Installation and Configuration of 2160 Field Communication Unit<br />
The Rosemount 2160 Field Communication Unit (FCU) has to be installed<br />
and configured prior to installing other devices such as a Rosemount 2410<br />
Tank Hub and a Rosemount 5900S Radar Level Gauge.<br />
To install a Rosemount 2160 FCU:<br />
• Assign a Modbus communication address<br />
• For each communication port, configure protocol and appropriate<br />
communication parameters<br />
• Configure the Slave Database with information about the devices<br />
connected to the fieldbus<br />
5-2 Section 5. Installing a Raptor Level Gauging System