For Measurement Mode Liquid Product Level enter the Product Dielectric<br />

Range. In some applications there is heavy vapor above the product surface<br />

having a significant influence on the level measurement. This may for<br />

example be the case of saturated water vapor under high pressure. In such<br />

cases the Vapor Dielectric Constant can be changed to compensate for this<br />

effect. Normally this value does not have to be changed since the effect on<br />

measurement performance is very small for most vapors. The default value is<br />

equal to 1 which corresponds to the dielectric constant of vacuum.<br />

For Measurement Mode Product Level and Interface Level enter the Upper<br />

Product Dielectric Constant. If the dielectric constant of the lower product is<br />

significantly smaller than the dielectric constant of water you may need to<br />

adjust the Lower Product Dielectric Range as well.<br />

See the Rosemount 5300 Reference Manual<br />

(Document No. 00809-0100-4530) for more information on tank environment<br />

settings.<br />

5-100 Section 5. Installing a Raptor Level Gauging System