Example 2: several Tanks connected to one 2410 Tank Hub<br />
This example includes three tanks, each of which has one Rosemount 5400<br />
Radar Level Transmitter and one Rosemount 2240S Multi-input Temperature<br />
Transmitter. All tanks are connected via the Tankbus to the same Rosemount<br />
2410 Tank Hub. The 2410 Tank Hub is connected to a TankMaster PC via a<br />
2160 Field Communication Unit.<br />
For each tank the Modbus addresses of the 5400 and other devices have to<br />
be entered in both the 2160 FCU Slave Database and the 2410 Tank<br />
Database.<br />
The 2240S and other non-level devices are handled as a single ATD device.<br />
In this example the 2410 Tank Hub serves three tanks. For Tank Position 1 in<br />
the 2410 Tank Database the ATD Modbus address is automatically set equal<br />
to the Modbus address of the 2410 Tank Hub itself. See “Tank Database<br />
Setup” on page 5-42 for further information.<br />
The Modbus address configuration is summarized in Table 5-3 below:<br />
Table 5-3. Configuration of the<br />
2160 FCU Slave Database and<br />
the 2410 Tank Database for<br />
three tanks and one 2410 Tank<br />
Hub<br />
Modbus Address<br />
Tank 5400 Level Transmitter ATD (2230, 2240S ) 2410 Tank Hub<br />
TK-1 1 101 101<br />
TK-2 2 102 - " -<br />
TK-3 3 103 - " -<br />
Figure 5-6. Configuration<br />
example with one 2410 Tank<br />
Hub and many tanks<br />
2160 FCU<br />
2240S<br />
2410<br />
2230<br />
5400<br />
TK-1<br />
2230<br />
5400<br />
2240S<br />
2240S<br />
TK-2<br />
2230<br />
5400<br />
TK-3<br />
The 2410 Level addresses in the 2160 FCU Slave Database must be equal to<br />
the Level Modbus addresses in the 2410 Tank Database.<br />
In this example the Level Modbus addresses of the three tanks are entered in<br />
positions 1A, 2A, and 3A in the 2160 FCU Slave Database and in tank<br />
positions 1, 2, and 3 in the 2410 Tank Database as illustrated in Figure 5-7:<br />
Section 5. Installing a Raptor Level Gauging System<br />