27.06.2021 Views

F. K. Kong MA, MSc, PhD, CEng, FICE, FIStructE, R. H. Evans CBE, DSc, D ès Sc, DTech, PhD, CEng, FICE, FIMechE, FIStructE (auth.)-Reinforced and Prestressed Concrete-Springer US (1987)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

212 Shear, bond and torsion

reduce the shear strength [1]. Therefore, in using Table 6.4-1,

any longitudinal bars which are terminated within a distance d

of the section concerned cannot be considered; indeed, near

such termination, it is desirable (though not mandatory) to put in

additional links locally [1].

(b) The use of Ve in shear design was explained in Section 6.3 in relation

to eqn (6.3-7). Earlier, it was explained in Section 6.2 that the

nominal shear stress at the collapse of a beam increases with the

concrete strength feu and the tension steel ratio e (= Asi bd). The Ve

values in Table 6.4-1, which already allow for the partial safety

factor Ym, are plotted against experimental data in Fig. 6.2-6. This

figure shows that some of the experimental values fall below the

BS 8110 design values.

(c) Equation (6.4-2) gives the requirements for minimum links. The

technical background to eqn (6.4-2) was given earlier in eqn (6.3-8):

(d)

evfyv ;::: 0.4

That is,

A sv f, > 04

b"sv yv - .

which becomes eqn (6.4-2), when the partial safety factor 0.87 is

used for fyv.

The requirement that the link spacing sv should not exceed 0.75d

follows from eqn (6.3-9). At right angles to the span, the horizontal

link spacing must also be kept sufficiently small to prevent the

pressing down of any longitudinal reinforcement bar and hence

maintain the dowel capacity.

Comments on Step 4

When v > 0.5ve , BS 8110 allows for the possibility of diagonal cracking; if

a diagonal crack does occur (because of accidental overloading, for

example) there should be sufficient shear reinforcement to arrest its

growth, and the minimum links specified by eqn (6.4-2) provide such a

safeguard.

Comments on Step 5

(a)

Equation (6.4-3) follows directly from eqn (6.3-5), if fyv is

multiplied by the coefficient 0.87 (= 1/1.15 where 1.15 is the partial

safety factor Y m).

(b) Note that irrespective of the amount of shear reinforcement used, the

shear stress v from eqn (6.4-1) must noI exceed O.8Heu or 5 Nlmm 2 •

See Step 2 again, if necessary.

(c)

BS 8110 does not permit shear reinforcement to be provided entirely

in the form of bent-up bars, because there is insufficient evidence to

show that beot-up bars 00 their own are satisfactory_ Bent-up bars,

however, may be used in combination with links (Fig. 6.3-2) but the

links must contribute at least 50% of the total resistance of the shear

reinforcement. The combined resistance of the links and bent-up bars

is to tie taken as the sum of their separate resistance; this point was

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!