Design and detailing-illustrative examples 79

In practice, Ac is usually taken for simplicity as the nominal cross-sectional

are a without deduction for the are a of the steel. In this case,

N = (0.4) (40) (300 2 ) + (0.75) (460) (1885) N

= 2090 kN

Example 3.6-2

Design a short, braced reinforced concrete column for an ultimate axial

load of 2000 kN. Given: fcu = 40 N/mm 2 , fy = 460 N/mm 2 .

SOLUTION

From eqn (3.4-2),

N = O.4fcuAc + 0.75fyA sc

Assume a 2% steel ratio, i.e. Ase = 0.02Ac, say,

(2000) (10 3 ) = (0.4) (40)Ac + (0.75) (460) (O.02A c)

Ac = 87340 mm 2 , say 300 mm square

If a 300 mm square section satisfies the fire-resistance and architectural

requirements, it is only necessary to calculate Ase from eqn (3.4-2).

(2000) (10 3 ) = (0.4) (40) (300 2 ) + (0.75) (460)A sc

Ase = 1623 mm 2

The are a of six size 20 bars is 1885 mm 2 from Table A2-1. Therefore adopt

the following values:

column section

main bars

links

nominal cover

300 mm square

6--size 20

size 8 at 200 mm centres

30 mm to links (see Tables 2.5-7 and 3.5-1)

Figure 3.6-1 shows the reinforcement arrangement for a typicallength of

column between ftoors. (See Comment (b) below on standard method of

detailing. See also Fig. 3.6-2.)

Comments

(a) The reinforcement details in Fig. 3.6-1 satisfy BS 8110's requirements

as listed in Section 3.5.

Main steel ratio = ~:; = 2.1% > 0.4% and < 6%

Link size

Link spacing

Nominal cover

8 mm > 1f4 of 20 = 5 mm

200 mm < 12 times 20 = 240 mm

30 mm to links, which is suitable for moderate

exposure (Table 2.5-7) and adequate for a 4-

hour fire resistance (Table 3.5-1)

(b) Figure 3.6-1 serves the purpose of showing the beginner a fairly clear

picture of how the reinforcement bars are arranged. However, the

way in which the reinforcement has been drawn and described is not

suitable for use in detail drawings for actual construction purpose.