446 Practical design and detailing

but at a distance from the support face equal to the effective depth d. This

is permitted by BS 8110-for details, see the Comments on Step 5 of the

solution to Example 6.4-2.

Comments on Step 7

See also Example 5.3-2 on possible remedial actions if the actual

span/depth ratio had exceeded the allowable.

Comments on Step 8

The clear distance ab between the bars, and the corner distance ac, are

calculated in the same manner as in Example 5.7-2. The ac values in Table

11.5-3 include an allowance for the fact that the links can only be bent to

an internal radius of 2(j) (see Fig. 6.6-1).

In Table 11.5-3, corner distances ac are not shown for the top bars at the

support B; the reason is as explained in Comment (b) at the end of

Example 5.7-2.

For the span AB, the moment redistribution is indicated as zero in Table

11.5-3. The reason can be found in Fig. 11.5-6, which shows that the

redistributed curve IIIR in fact coincides with the elastic curve I.

Comments on Step 9

The internal tie requirement dictates the provision of the bottom bars 2T32

at the internal support B. This explains why, in Step 5, 2T32 (1608 mm 2 )

were provided even though the area required at the time was only 476

mm 2 •

Comments on Step 10

The main bars in Fig. 11.5-12 have been curtailed in accordance with the

curtailment diagram in Fig. 11.5-10. (See also the 'Simplified rules for

curtailment of bars' in Section 4.10.)

Example 11.5-3

With reference to the braced building frame in Fig. 11.5-1, design and

detail an internal column, B9.

SOLUTION

See Fig. 11.5-13 (feu = 40 N/mm 2 ), and Comments at the end.

Step 1 Durability and .fire resistance

From Table 2.5-7,

nominal cover for mild exposure = 20 mm

cover to main bars = 30 + link (jJ = 40 mm, say

From Table 3.5-1,

(use 30 mm)

for 380 square column with 40 mm cover to main bars,

the fire resistance exceeds 1 hour

Nominal cover = 30 mm

Fire resistance 0 K