452 Practical design and detailing

Comments on Step 4

As explained (in the first sentence) in Section 7.3, BS 8110 defines a short

column as one for which the ratios lcxlh and lcylb are both less than 15.

Comments on Step 5

The roof loads are taken from design calculations for the roof main beam,

which are not shown here owing to space restriction.

Comments on Step 6

BS 8110's definition of the design minimum eccentricity is explained in the

definition of M following eqn (7.3-2).

Comments on Step 7

See 'Limits on main reinforcement' in Section 3.5. For the column lengths

from the 1st floor to the roof, we could have used smaller bars than size 25.

However, size 25 bars have the advantage of providing a robust cage with

the links. Besides, it is good practice to limit the spacing of the column

main bars to not exceeding 250 mm. With size 25 bars, the spacing is just

about 250 mm.

Site Ref.: Job No.1959/65/67

Trinity and Newnham Colleges

Date: 4 December 1987

Bar Type No No Total Length

Member mark and of in no. each

size mbrs each bar

mm

Shape

Shape Code

(BS4466)

A B 0

mm mm mm

1 T32 1 4 4 4800

~ 41

-OT

3075 700 70

Column

89

2 T25 2 4 8 4800

~ 41

or

3450 550 55

3 T25 1 4 4 3875

~

or

41

2535 550 55

4 R8 4 13 52 1400

Ej

60

310 310

Fig. 11.5-16 Bar bending schedule-Trinity and Newnham Colleges

(see also Fig. A2-2)