450 Practical design and detailing

Total axial loads (see Table 11.5-4)

3rd floor to roof

2nd to 3rd floor

1st to 2nd floor

Foundation to 1st floor

N3r 168 + 461 629 kN

N23 = 382 + 948 = 1330 kN

N 12 = 547 + 1435 = 1982 kN

Nn = 659 + 1922 = 2581 kN

N3r = 629 kN N23 = 1330 kN N12 = 1982 kN: Nn = 2581 kN

Step 6 Design bending moments

BS 8110's design minimum eccentricity (see Comments at the end) =

0.05h.

Minimum design moment = 0.05hN

Foundation to lst floor level:

0.05h Nn = 0.05 X 380 X 10-3 X 2581 (see Step 5)

= 49 kNm

Elsewhere, N < Nn and hence 0.05hN < 49 kNm.

Therefore the column design is governed by the column moments in

Step 3 as these are larger than 0.05hN.

Step7

M (roof junction) = 109 kNm

Reinforcement

Jcu -r = 40 N/mm 2 ·' Jy

-r = 460 N/mm 2

4 _ 380- 40- (bar ifJ)/2 _

h - 380 - 0

. 85

approx.

M (floor junction) = 107 kNm

Hence the design chart in Fig. 7.3-1 applies, and the results are as

shown in Table 11.5-5.

Step 8 Reinforcement details (see Fig. 11.5-15)

Comments on Step 1

Note BS 8110's definition of the term 'nominal cover', as explained under

Table 2.5-7 in Section 2.5(e).

Table 11.5-S Column reinforcement

N M

bh w Asc required 3 Asc provided

Location (N/mm 2 ) (N/mm 2 ) (Fig. 7.3-1) (Fig. 11.5-15)

3rd ft. to roof 4.4 2.0 0.4% bh = 578 mm 2 41'25 (1960 mm 2 )

2nd to 3rd fl. 9.2 2.0 0.4% bh = 578 mm 2 41'25 (1960 mm 2 )

1st to 2nd ft. 13.8 2.0 0.4% bh = 578 mm 2 41'25 (1960 mm 2 )

Fndn to 1st fl. 17.9 2.0 1.4% bh = 2021 mm 2 41'25 (3216 mm 2 )

• From Section 3.5, the minimum steel ratio is 0.4%.