Principles of column interaction diagrams 261

1.983, (a, {3) falls on the a axis and remains there for all larger values

of x/h. Note that the points (a,{3) for xlh > 1.111 in fact fall within

the region excluded by the BS 8110 line eminlh = 0.05, referred to in

Example 7.1-4(b). Therefore, cases where xlh > 1.111 are of little

practical interest.

Example 7.1-6

In this section, our emphasis has been on the fundamental principles, the

aim being to obtain an insight into the properties of column interaction

diagrams. The worked examples have been designed with the above aim in

mind. (Indeed, Example 7.1-3 has been adapted from a past examination

paper of Cambridge University.) However, if our aim is merely the

straightforward construction of column interaction diagrams for use as

routine design charts, then we can use a very simple procedure, such as

that explained below.

SOLUTION

For the typical section in Fig. 7.1-10, it is immediately seen that the direct

compression is

N = 0.45fcubdc + ~~~A~l - fs2As2 (7.1-20)

Taking moments about the mid-depth of the section,

M = 0.45fcubdc(~- ~c) +~~~A~~(~- d')

+ fs2As2(~- d2) (7.1-21)

where de= 0.9x and compressive stresses in the reinforcement are taken as

positive.

Next proceed as follows.

Step I

Assume a value for xlh.

Column section

(a)

Forces

(b)

Fig. 7.1-10