SCOPF Bus Marginal Price Details<br />

This display (from the SCOPF Results page) shows information about the components of the marginal<br />

cost at each bus. The display is relevant to see how the bus marginal cost depends on the cost of<br />

enforcing system constraints such as branch limits and area equality constraints. This display is useful<br />

for indicating which constraints are contributing towards the determination of the marginal price at<br />

each bus.<br />

As any case info display in <strong>Simulator</strong> this display can be customized and the information copied,<br />

printed, and saved by accessing the local menu option with the mouse right click.<br />

One key feature of this display is the breakdown in the bus MW marginal cost into three components:<br />

the cost of energy, the cost of congestion, and the cost of losses. Also, while the bus MW marginal<br />

cost does not change based on the reference, the costs of energy, congestion, and losses are<br />

reference dependent. This reference is set on a per-area (or per-super area) basis in the Area<br />

information dialog OPF tab (or the Super Area information dialog OPF tab).<br />

©2011 <strong>PowerWorld</strong> Corporation<br />