specify power flow at the inverter end. If the DC line operates in Current Control Mode, enter the<br />

desired line flow in amps.<br />

Resistance<br />

Resistance of the DC Line.<br />

Sched. Voltage<br />

Scheduled DC line voltage in kV. The value of Rcomp is used to determine whether this value<br />

specifies the inverter end or the rectifier end.<br />

Switch Voltage<br />

When the line operates in the Power Control Mode, this is the inverter voltage level in kV at which<br />

the line switches from constant power to constant current control.<br />

RComp<br />

Compounding resistance. The compounding resistance dictates whether the inverter voltage is<br />

scheduled (Rcomp = 0), or the rectifier voltage is scheduled (Rcomp = DC line resistance). <strong>Simulator</strong><br />

does not currently support scheduling the voltage at a point along the DC line (0 < Rcom < DC line<br />

resistance), but instead will treat any non-zero value of Rcomp as scheduling the voltage at the<br />

rectifier.<br />

Setpoint Specified At<br />

Indicates which end of the DC transmission line the Setpoint value is designated. This will be the<br />

terminal where the setpoint value is maintained. The opposite terminal flow value will be a<br />

calculated quantity.<br />

Metered End of Line<br />

Indicates which end of the DC line is assumed metered for Area interchange calculations.<br />