Include Marg. Losses<br />

Specifies whether or not marginal losses should be included for the area during the OPF solution.<br />

MW Marg. Cost Ave<br />

For an OPF solved case this field shows the average of the bus MW marginal costs for all the buses<br />

in the area. If there is no congestion then all of the marginal costs should be equal.<br />

MW Marg. Cost St.Dev., Min., Max.<br />

For an OPF solved case these fields show the standard deviation of the bus MW marginal costs for<br />

all the buses in the area, the minimum and the maximum bus MW marginal costs.<br />

Report Limits<br />

Specifies whether or not the kV limits should be reported. If this is set to NO, all of the other area<br />

options described above will be ignored because the area will not be included in any monitoring<br />

during the OPF.<br />

Report Min kV, Report Max kV<br />

Specifies the values for minimum and maximum kV levels to report. Defaults are 0 and 9999. This<br />

allows further determination of what elements that belong to the area will be included in the OPF<br />

enforcement. Only elements with nominal voltages in the specified Min/Max kV range will be<br />

included.<br />