09.03.2013 Views

Simulator 16 User Guide - PowerWorld

Simulator 16 User Guide - PowerWorld

Simulator 16 User Guide - PowerWorld

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

PV Curves Results: Overview<br />

The Overview sub-tab is found on the PV Results tab of the PV Curves dialog. This page provides a<br />

summary of all scenarios studied and their results. This table will update as the analysis progresses.<br />

The overview is a case information display and therefore can be used in a manner consistent with all<br />

other case information displays.<br />

There are a number of fields that are shown by default on the display:<br />

PV Scenario<br />

Name of the scenario. Either base case or the contingency name.<br />

Critical?<br />

YES if the scenario is considered to be critical. Otherwise, NO.<br />

Critical Reason<br />

This will be blank as long as the scenario is not critical. If the scenario is critical, there are a number<br />

of reasons that could be displayed explaining why the scenario is critical:<br />

Reached Nose - The power flow failed to solve so the system is considered to be at the nose of the<br />

PV curve.<br />

Inadequate Voltage - The process stopped because at least one voltage is considered inadequate.<br />

This reason will only occur when using the option specified on the Limit Violations tab to Stop<br />

when voltages become inadequate. The message will be appended with the bus and voltage of<br />

the bus with the lowest inadequate voltage.<br />

Source Maxed - The source no longer has enough resources to continue the power transfer.<br />

Source resources are affected by the options Enforce unit MW limits and Do not allow<br />

negative loads found on the Common Options sub-tab of the Setup tab. They could also be<br />

affected if choosing to use merit order dispatch in which unit limits are always enforced.<br />

Sink Maxed - The sink no longer has enough resources to continue the power transfer. Sink<br />

resources are affected by the options Enforce unit MW limits and Do not allow negative loads<br />