Transformer Impedance Correction Table Display<br />

The Transformer Impedance Correction Display shows information about all the transformer<br />

impedance correction tables in the case. The Transformer Impedance Correction Display is used to<br />

model the change in the impedance of the transformer as the off-nominal turns ratio or phase shift<br />

angle is varied.<br />

The Correction Display is a class of Case Information Display and therefore can be used in a manner<br />

consistent with all other case information displays. It has a local menu from which you can print, copy,<br />

and modify its information as well as view the information dialog of its associated correction tables.<br />

When in Edit Mode, you can define new tables using the Insert option, or delete existing tables using<br />

Delete. You can also sort the transformer impedance correction information by clicking on the heading<br />

of the field by which you want to sort.<br />

To show this display select Network > Impedance Correction Tables from the Model Explorer.<br />

The display contains the following fields by default:<br />

Table #, Table Name<br />

Shows the table number and name for the record. Table number must be between 1 and 64.<br />

Transformer Impedance Scaling Factors<br />

The rest of the default columns show the actual fields in the table. The first field of each pair shows<br />

the off-nominal turns ratio or phase shift angle, while the second field shows the associated scaling<br />

factor for the transformer’s impedance.<br />