Transformer Impedance Correction Tables Dialog<br />

The Transformer Correction Tables Dialog is used to view information about the transformer<br />

impedance correction tables. These tables are used on some LTC or phase shifting transformers to<br />

model the impedance of the transformer as a function of the off-nominal turns ratio or phase shift.<br />

The dialog has the following fields:<br />

Transformer Impedance Correction Table Number<br />

Number of the impedance correction table, between 1 and 63. Use the spin button immediately to<br />

the right of this field to step through the list of defined tables. If you have made changes to a<br />

particular table, you must click Save before moving to another correction table; otherwise, your<br />

changes will be lost.<br />

Table Name<br />

The name assigned to the table.<br />

Table Entries<br />

Used to insert/edit/delete the actual entries in the impedance correction table. In the first row, enter<br />

either an off-nominal turns ratio for an LTC transformer, or a phase shift in degrees for a phase<br />

shifting transformer. The entries in the first row must be entered in strictly ascending form. In the<br />

second row, enter the scale factor to apply to the transformer impedance. The transformer's nominal<br />

impedance is multiplied by the scale factor to obtain the actual value. Note that at least two columns<br />

must be used.<br />

Right-click on the table to invoke its local menu, which allows you to delete and to insert columns.<br />

To insert a new column, click on the column before which you want to insert a new column and<br />

select Insert New Point from the local menu. To delete a column, position the cursor on the<br />

column you want to delete and select Delete Point.<br />

Table is Used by the Following Transformers<br />

Lists all the transformers in the case that use this impedance correction table. A single table may be<br />

used by any number of transformers. To associate a table with a transformer, use the Transformer<br />

AVR Dialog for LTC transformers or the Transformer Phase Shifting Dialog for phase shifters.<br />