The amount of Mvar shift that would be implemented by switching one tap position from the<br />

current position. This sensitivity indicates the ability of the transformer to control Mvars.<br />

Impedance Correction Table<br />

Specifies the number of the transformer's corresponding transformer impedance correction table.<br />

Transformer impedance correction tables are used to specify how the impedance of the<br />

transformer should change with the off-nominal turns ratio. If this number is 0, no impedance<br />

correction table is associated with the transformer, and the impedance of the transformer will<br />

thus remain fixed as the tap ratio changes. Valid impedance correction table numbers range from<br />

1 to 63. To assign an existing impedance correction table to the transformer, enter the existing<br />

table's number. To view the existing impedance correction tables, click the Insert/View<br />

Impedance Correction Table button, which brings up the Transformer Impedance Correction<br />

Dialog. To define a brand new impedance correction table for the transformer, enter an unused<br />

table number and then click Insert/View Impedance Correction Table to prescribe the<br />

correction table. Note that the association between a transformer and an impedance correction<br />

table is not finalized until you select either OK or Save on the Branch Information Dialog or<br />

Branch Options dialog.<br />

View Transformer Correction Table or Insert Transformer Correction Table<br />

Click on this button either to view or to insert transformer correction tables. Clicking on this<br />

button displays the Transformer Impedance Correction Dialog. Note that a table must contain at<br />

least two points in order to be defined.<br />

The Time Step Options tab contains control options specific for the Time Step Simulation tool.<br />

©2011 <strong>PowerWorld</strong> Corporation<br />

373