09.03.2013 Views

Simulator 16 User Guide - PowerWorld

Simulator 16 User Guide - PowerWorld

Simulator 16 User Guide - PowerWorld

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

then typing in the new value. Other values are toggleable and can be changed by double-clicking on<br />

the value. For reference regarding what the various "size" defaults mean, when the zoom level is at<br />

its nominal value (100%), the size of the screen is 100 by 100. There are also some special kinds of<br />

fields in this dialog which are discussed next.<br />

Editing Colors and KV-Based Color Coding<br />

In order to modify a color value, double-click on the colored rectangle to bring up the Color Dialog.<br />

Then specify the color you want. For some defaults, such as fill color, it is possible to specify the<br />

default color to be none. In order to set a color default to none, select the colored rectangle and<br />

press the Delete key.<br />

At times, a user may want to see the kV level of screen objects directly from the oneline diagam,<br />

without having to open a text display. One way to do this is to color code the elements on the<br />

oneline diagram according to kV level. Right-click on the table and choose Insert from the local<br />

menu. Specify the Nom kV and color.<br />

Editing Default Field Positions ("Pos1", "Pos2", etc…)<br />

Many objects allow you to specify some default fields to be automatically added when a new object<br />

is drawn. For example, you may want to insert the bus name next to all new Bus Objects. For<br />

objects that allow the insertion of fields, a tab with field position diagrams will be available when<br />

that object type is selected. In order to specify the default positions of fields, click on the tab<br />

showing the field positions and click on the table row corresponding to the Nom kV of the defaults of<br />

interest. For object types that do not allow specifying the defaults by Nom kV, simply update the<br />

given position diagram. The position diagram will show the present settings for the new fields.<br />

Positions that have a default specified will be highlighted and the name of the default field will be<br />

shown. Positions with no default field will not be highlighted and will say "Pos1", "Pos2", etc…. For<br />

objects that have more than one possible orientation (e.g. generators can be up, right, left or<br />

down), there are multiple position diagrams showing the positions for each orientation.<br />

In order to modify the settings, move your mouse over the position on the dialog you want to<br />

change and click. This will bring up the appropriate Field Options Dialog such as the Bus Field<br />

Options, Generator Field Options, Load Field Options, Switched Shunt Field Options, Line Field<br />

Options, Interface Field Options, Substation Field Options, Area Field Options, Super Area Field<br />

Options, or the Zone Field Options. Simply select the field you want and choose OK. If you would<br />

like to set a default field to "none", click Remove Field instead of OK. You can also modify default<br />

fields by double-clicking on the table for "Pos1", "Pos2", etc… This brings up the appropriate Field<br />

Options Dialog as well. If you press the Delete key while on a "Pos" field in the table, it will set the<br />

default field to "none".<br />

Editing Stub Size and Stub Space<br />

When utilizing the Automatically Insert Transmission Lines feature, the Stub Size and Stub Space<br />

values are used. <strong>Simulator</strong> will draw each automatically inserted branch such that it emerges from<br />

both its terminal buses at right angles. To accomplish this, <strong>Simulator</strong> draws each automatically<br />

inserted branch in three segments: two stubs perpendicular to the terminal buses having a length<br />

specified by the value supplied for Stub Size, and a third segment joining the two stubs. The<br />

amount of space between lines as they converge into a bus is set by Stub Space.<br />

If you do not want transmission line stubs to be inserted, then set Stub Size to none or to a<br />

negative number. Note in order to set a value for Stub Space, Stub Size must be set to a positive<br />

number first.<br />

Editing CB Size<br />

When you insert new transmission lines or transformers, circuit breakers will automatically be<br />

inserted on the branch with their size specified by CB Size. If you do not want Circuit Breakers<br />

inserted for a particular voltage level, then set CB Size to none or a negative number.<br />

©2011 <strong>PowerWorld</strong> Corporation<br />

692

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!