OPF Area Records<br />

Displays OPF specific information about each area record in the case. To show this display select<br />

Optimal Power Flow > Results > Areas in the Model Explorer or OPF Areas from the OPF Case<br />

Info menu found in the Optimal Power Flow (OPF) ribbon group on the Add Ons ribbon tab while<br />

in Run mode. The OPF Area Records Display is a class of Case Information Display and therefore can<br />

be used in a manner consistent with the other case information displays. Specific formatting options<br />

are available from the local menu, which can be accessed by right-clicking on any field in the display.<br />

By default the display contains the following fields:<br />

Number, Name<br />

Area’s integer number and its alphanumeric identifier, 255 characters maximum.<br />

AGC Status<br />

Area's automatic generation control status. This is the same field shown on the Area Records<br />

Display. The field indicates whether or not the area's generation is changing automatically to control<br />

the area interchange.<br />

To be included in the OPF, this field MUST be OPF. The generation costs for areas that are on OPF<br />

control are included in the OPF objective function; otherwise they are not. Note that if the area is<br />

part of a super area that is on AGC control, this field value is ignored.<br />

Double-click on the field to toggle its value.<br />

XF Phase<br />

Specifies whether phase shifting transformers in the area are available as controls. If Yes then all<br />

transformers in the area which have their Automatic Control Active are available for control; the<br />

Automatic Control status for a transformer is set on the Branch Information Dialog. If No then no<br />

transformers in the area are available for control.<br />

Branch MVA<br />

Specifies whether or not the MVA limits should be enforced for transmission lines and transformers<br />

that have at least one terminal in this area. For a transmission line or transformer to be included,<br />

Line/Transformer MVA Limit Enforcement must not be disabled on the OPF Options and Results<br />

Dialog, and the individual line/transformer must be enabled for enforcement on the OPF<br />

Line/Transformer display.<br />

Interface MW<br />

Specifies whether or not the MW limits should be enforced for interfaces that have at least one<br />

element in this area. For an interface to be included, Interface MW Limit Enforcement must not be<br />

disabled on the OPF Options and Results Dialog, and the individual interfaces must be enabled for<br />

enforcement on the OPF Interface display.<br />

Load MW Dispatch<br />

Specifies whether or not the MW load demand in an area should be included as available for redispatch<br />

during an OPF solution. In order for loads to be included in OPF re-dispatch, each individual<br />

load within the area must be available for control, and have either a fixed cost benefit or a<br />

piecewise-linear cost benefit curve provided. The option to Disable All Load MW Controls must also<br />

not be selected on the OPF Options and Results Dialog.<br />

DC Line MW Control<br />

Specifies whether or not DC line MW setpoints can be modified for DC lines that have at least one<br />

terminal in this area. For a DC line to be included, DC Transmission Line MW Controls must not be<br />

disabled on the OPF Options and Results Dialog.<br />