ROHS Substances table<br />

117<br />

ROHS Name<br />

CAS<br />

TWAEV<br />

STEV<br />

Ceil<strong>in</strong>g<br />

(mg/m³)<br />

Notes<br />

<strong>Sampl<strong>in</strong>g</strong><br />

Device<br />

Flow<br />

L/m<strong>in</strong><br />

Volume<br />

TWAEV<br />

STEV<br />

(L)<br />

Pr<strong>in</strong>ciple<br />

MRV<br />

µg<br />

CVa<br />

(%)<br />

#<br />

meth.<br />

Remarks<br />

Silicon carbide (non<br />

fibrous)<br />

409-21-2<br />

10 Pt SKC 225-8-01-1 or 225-8-04 polyv<strong>in</strong>yl 1,5 180 Grav 25 4,9 IRSST<br />

48-1<br />

chloride filter<br />

902 PVC filter-37<br />

914 PVC filter-25<br />

Additional <strong>in</strong><strong>for</strong>mation is available <strong>in</strong> Info-Labo 91-03. The weight measurement<br />

method <strong>for</strong> dusts is by def<strong>in</strong>ition non-specific.<br />

Silicon tetrahydride<br />

7803-62-5<br />

6,6 Glass fritted tip imp<strong>in</strong>ger conta<strong>in</strong><strong>in</strong>g 15 mL 1 480 ICP<br />

OSHA<br />

IMIS2237<br />

of potassium hydroxide<br />

OSHA<br />

ID125G<br />

The samples must be stored <strong>in</strong> plastic conta<strong>in</strong>ers and shipped as soon as<br />

possible. Contact <strong>the</strong> IRSST be<strong>for</strong>e sampl<strong>in</strong>g.<br />

OSHA method ID-125G is <strong>for</strong> total silicon and can be adapted to this product.<br />

Silver, Metal<br />

7440-22-4<br />

0,1 Omega M-083700AF or Omega M-<br />

1,5 180 ICP-MS 0,05<br />

IRSST<br />

375<br />

082500AFP mixed cellulose ester filter<br />

905 MCE filter-37<br />

915 MCE filter-25<br />

Specific sampl<strong>in</strong>g must be carried out <strong>for</strong> this substance.<br />

The analytical results are expressed as total silver.<br />

Silver [7440-22-4],<br />

Soluble compounds (as<br />

Ag)<br />

7440-22-4<br />

0,01<br />

Contact <strong>the</strong> IRSST be<strong>for</strong>e sampl<strong>in</strong>g.<br />

IRSST method 20-3 is <strong>for</strong> total silver and can be adapted to soluble silver<br />

compounds.<br />

Soapstone<br />

14378-12-2<br />

6 Pt SKC 225-8-01-1 or 225-8-04 polyv<strong>in</strong>yl 1,5 180 Grav 25 4,9 IRSST<br />

48-1<br />

chloride filter<br />

902 PVC filter-37<br />

914 PVC filter-25<br />

Additional <strong>in</strong><strong>for</strong>mation is available <strong>in</strong> Info-Labo 91-03. The weight measurement<br />

method <strong>for</strong> dusts is by def<strong>in</strong>ition non-specific.<br />

Soapstone<br />

14378-12-2<br />

3 Pr SKC 225-8-01-1 or 225-8-04 polyv<strong>in</strong>yl 1,7 180 Grav 25 4,9 IRSST<br />

48-1<br />

chloride filter<br />

(nylon)<br />

902<br />

914<br />

PVC filter-37<br />

PVC filter-25<br />

2,75<br />

(GS3)<br />

997 PVC filter-37, 3 parts<br />

Additional <strong>in</strong><strong>for</strong>mation is available <strong>in</strong> Info-Labo 91-03. The weight measurement<br />

method <strong>for</strong> dusts is by def<strong>in</strong>ition non-specific.<br />

Sodium azide<br />

26628-22-8<br />

--<br />

--<br />

0,3<br />

RP Polyv<strong>in</strong>yl chloride filter <strong>in</strong> series with a<br />

1 5 IC-VIS<br />

OSHA<br />

ID211<br />

silica gel tube 150/75 mg.<br />

Contact <strong>the</strong> IRSST be<strong>for</strong>e sampl<strong>in</strong>g.<br />

OSHA method ID211 is <strong>for</strong> <strong>the</strong> simultaneous determ<strong>in</strong>ation of sodium azide<br />

(NaN3) and hydrazoic acid (HN3) s<strong>in</strong>ce sodium azide is converted <strong>in</strong>to hydrazoic<br />

acid on contact with moisture.<br />

Sodium bisulfite<br />

7631-90-5<br />

5<br />

Contact <strong>the</strong> IRSST be<strong>for</strong>e sampl<strong>in</strong>g.<br />

IRSST method 287-1 is <strong>for</strong> <strong>the</strong> analysis of total soluble sodium and can be<br />

adapted to this product.