The external circuit to control the motor brake is built as shown below.<br />

Please set the waiting time for brake release at<br />

SEt-32. The setting range is 0 to 10000 10 ms and<br />

the default value is 0.<br />

If the motor brake is working at the moment when the drive activates<br />

the motor, it should be released first. In this case, if the brake is<br />

released before the servo is ON, the vertical load will drop for a<br />

moment. Therefore, the servo should be ON first so that the drive can<br />

control the vertical load so that it won’t fall, and then the brake should<br />

be released. This configuration is to secure the time for the servo drive<br />

to release the motor brake from the moment the servo is ON.<br />

Brake Inactive delay Time<br />

Please set the servo OFF delay time at SEt-29. The<br />

setting range is 0 to 1000 [10 ms] and the default<br />

value is 0. This configuration is used to secure the<br />

time before the drive activates the motor brake<br />

after the controller delivered the servo OFF<br />

command.<br />

<strong>Servo</strong> Off Delay Time<br />