If the torque command gain is 100%/3V and the input voltage is 9V,<br />

300% torque, the maximum torque of the motor, will be generated.<br />

ATTENTION<br />

The maximum allowed voltage of the torque command input<br />

is DC ±10V.<br />

If the standard voltage fluctuates, the torque command can<br />

also change together. Therefore, a power supply with high<br />

accuracy is needed.<br />

If minute torque adjustment is required, please use a multirevolution<br />

variable resistor which revolves over 10 times.<br />

If the torque command is bigger than the preset maximum<br />

torque of the motor, an warning for excessive torque<br />

command (A.08 OtC) will be issued.<br />

The motor sometimes revolves in both cases where the controller<br />

didn’t approve a torque command at the offset automatic adjustment<br />

and where the controller approved the torque command with 0V. This<br />

is because of the voltage offset between the controller and the drive.<br />

Torque Limit<br />

The torque of the servo motor can be limited in either forward or<br />

reverse direction.<br />

There are two methods to limit torque.<br />

The first is internal limit. The internal limit is the limit of the drive itself<br />

by setting parameters regardless of external signals.<br />

The second is external limit. The external limit is determined<br />

according to input signals.<br />

Please set SEt-10 to limit the forward torque<br />

internally. The setting range is 0 to 300% and the<br />

default value is 300.<br />

Please set SEt-11 to limit the reverse torque<br />

internally. The setting range is 0 to 300% and the<br />

default value is 300.<br />

Please set SEt-12 to limit the forward torque<br />

externally. The setting range is 0 to 300% and the<br />

default value is 100.<br />

Please set SEt-13 to limit the reverse torque<br />

externally. The setting range is 0 to 300% and the<br />

default value is 100.<br />