Allowed Inertia Ratio (Based on the 50% usage rate of the regenerative resistor)<br />

1.2kW 1.3kW 1.5kW 2kW 2.5kW 3kW 3.5kW 4kW 4.5kW 5kW 6kW<br />

CSMD 8.0 5.0 6.0 5.0 3.0 3.0 2.0 1.5<br />

CSMS 16.0 11.0 9.0 8.0 7.0 4.0 4.0 3.0<br />

CSMF 6.0 2.0 2.0 1.0<br />

CSMH 2.0 1.0 0.5 0.3 0.0<br />

CSMK 13.0 10.0 6.0 7.0 5.0<br />

RSMD 8.0 5.0 6.0 5.0 3.0 3.0 2.0 1.5<br />

RSMF 6.0 2.0 2.0 1.0<br />

RSMH 2.0 1.0 0.5 0.3 0.0<br />

RSMK 13.0 10.0 6.0 7.0 5.0<br />

RSMX 5.0 3.0 1.0 1.0<br />

RSMN 8.0 4.5 2.0<br />

RSML 6.0 3.0 2.0 2.0 1.5<br />

Allowed inertia ratio application condition<br />

Setting acceleration time<br />

1cycle<br />

Operation Speed<br />

200 ms<br />

2 sec.<br />

Rated Speed<br />

A regenerative resistor that users connect to the outside according to<br />

the load is called the external regenerative resistor. The rated power of<br />

the regenerative resistor consumes the regenerative energy produced<br />

from the load system. If the produced energy is small enough, users<br />

can set up the external regenerative resistor and increase the rated<br />

power of the regenerative resistor, so that the regenerative energy<br />

produced from the load system can be consumed.<br />

There are two ways to increase the allowed power of the regenerative<br />

resistor. The first is connecting the internal regenerative resistor and<br />

the external resistor in parallel, and the second is mounting an extra<br />

external regenerative resistor after removing the internal regenerative<br />

resistor.<br />

ATTENTION<br />

In case of increasing the rated power of regenerative resistor,<br />

set the minimum resistor value according to capacity. (15Ω to<br />

25Ω)<br />

ATTENTION<br />

The temperature of a resistance for the regenerative resistor<br />

can rise over 200° C under the rated load condition. Because<br />

without an extra cooling fan, the temperature of the<br />

regenerative resistor can go up excessively, please use 20%<br />

or less of the rated power of the regenerative resistor.<br />