31.12.2014 Views

Volume 8 – Mechanical and Electrical Services - Malaysia Geoportal

Volume 8 – Mechanical and Electrical Services - Malaysia Geoportal

Volume 8 – Mechanical and Electrical Services - Malaysia Geoportal

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Chapter 7 ELECTRICAL SERVICES<br />

As for electrical requirement TNB requires the consumer to provide lighting points <strong>and</strong> switch socket<br />

outlets to be terminated at a DFB or splitter unit. If L.V. supply is not available in TNB substation, it<br />

has to be provided by the consumer by taking supply from the main switchboard.<br />

7.3.4 Main Switch Room<br />

Main switch room (also subswitch rooms, if any) should be big enough to permit easy installation<br />

<strong>and</strong> maintenance. Usually not less than 0.7m clearance should be allowed between the wall <strong>and</strong> the<br />

rear of the switchboard. Front clearance of the switchboard should be such that there is still<br />

sufficient passage space with the switch gears full withdrawn. The minimum length of the switch<br />

room should be equal to the length of the switchboard plus 1.2m.<br />

Cable trench in the switch room is usually about 0.75m wide so that while the trench is not<br />

unnecessarily congested with cables, the switchboard can still sit with 150mm to each side of the<br />

trench.<br />

Main switch room should have external door for easy access from the exterior of the building.<br />

7.3.5 Main Switch Board<br />

Main switchboard is normally of the self-contained, floor mounted, flush fronted, metalclad cubicle<br />

type suitable for front <strong>and</strong> rear access. It shall be designed to with st<strong>and</strong> fault condition of not less<br />

than 31 MVA at 415V for 1 second as defined in B.S.5486.<br />

Air circuit breaker is normally used as incoming switchgear. It shall have minimum breaking capacity<br />

of 31 MVA at 415V with a short time rating of 1 second. Other components are protection relays,<br />

ammeters, voltmeters, power factor meters, or micro-processed based digital power meters, current<br />

transformer, etc. The MSB must be capable of withst<strong>and</strong>ing certain fault <strong>and</strong> load conditions <strong>and</strong><br />

should be positioned at a suitable location with respect to accessibility, ease of operation <strong>and</strong> length<br />

of cable run with adequate ventilation ensured. It shall be fabricated by Switch Board manufacturer<br />

approved by Suruhanjaya Tenaga.<br />

Sometimes two transformers are supplied by TNB. This may happen when:-<br />

a) A single transformer is insufficient to cater for the total load of the installation, or<br />

b) A more secured supply system for the installation is required.<br />

Whatever the cause maybe, the main switchboard must be designed to receive the two incoming<br />

feeders from the separate transformer. In this case it is normal practice to incorporate a 4 pole<br />

coupler between the two sections of main busbars fed by the two transformers to provide further<br />

flexibility in the supply system. The coupler must at least be mechanically interlocked with the other<br />

two incoming A.C.B.’s is opened in order to satisfy TNB’s requirement.<br />

7.3.5.1 Circuit Protection<br />

Generally the main incoming breaker should be provided with both O/C & E/F (either IDMT or<br />

instantaneous type) protection. Outgoing breakers may be provided with O/C or O/C & EF<br />

(instantaneous type) depending on the circuit design.<br />

As the majority of electrical faults in government buildings are attributed to earth fault, it is advisable<br />

to provide the main incoming breaker with IDMT E/F protection to achieve a better discrimination<br />

between the outgoing circuits <strong>and</strong> the main incoming breaker thus reducing the occurance of the<br />

total power failure to the building.<br />

7-10 March 2009

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!