Volume 8 – Mechanical and Electrical Services - Malaysia Geoportal
Volume 8 – Mechanical and Electrical Services - Malaysia Geoportal
Volume 8 – Mechanical and Electrical Services - Malaysia Geoportal
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Chapter 7 ELECTRICAL SERVICES<br />
7.3.5.2 Switchgears<br />
The switchgears normally encountered are the ordinary lamp <strong>and</strong> socket outlet switches, isolators<br />
fuse switches, switchfuse, circuit breakers, changeover switches <strong>and</strong> contactors.<br />
Given below are some useful notes on the more commonly used protective <strong>and</strong> isolating devices.<br />
a) Isolators - These are used for local isolation only. They are not used for<br />
cable protection.<br />
b) Switch fuse/ switch fuse- This is a single unit made up of an isolator in series with an<br />
HRC fuse the HRC Fuse being retractable. It comes in both<br />
SP & N <strong>and</strong> TP & N configurations with st<strong>and</strong>ard rating being<br />
20A, 30A, 45A <strong>and</strong> 60A.<br />
c) MCCB This is both an isolating as well as a protective device to<br />
control loads above 100A to 400A<br />
d) Air-circuit-breakers - These together with over-current <strong>and</strong> earth leakage relays<br />
are used for busbar ratings of 400A <strong>and</strong> above. They are<br />
expensive but efficient tripping devices.<br />
MCBs <strong>and</strong> MCCBs are generally being introduced to replace h.r.c.fuses, switch fuses, <strong>and</strong> even air<br />
circuit breakers on account of their compact size, ease of maintenance <strong>and</strong> neat appearance when<br />
incorporated into cubicles.<br />
The choice of circuit breaker must conform to the fault level designed for. The interrupting capacity<br />
of the circuit breaker must be equal to or greater than the amount of fault current that can be<br />
delivered at the point in the system where the breaker is applied. The amount of fault current<br />
supplied by a system can be calculated at any point in the system.<br />
The following interrupting capacities should be considered for the 240/415V system:-<br />
Main Switch Board : 43 KA(31MVA) to 32 KA(23MVA)<br />
SUB Switch Board : 22KA 916MVA) to 14 KA(10MVA)<br />
Distribution Board : 10KA to 6 KA<br />
7.3.6 Distribution Board<br />
Distribution board normally is wall mounted type. It consists of isolating switchgears, final sub circuit<br />
breakers for over current <strong>and</strong> earth leakage protection. The mounting height for a distribution board<br />
shall be 2m measured from the floor to the underside of the distribution board.<br />
7.3.7 Generator Set<br />
7.3.7.1 Generator room selection <strong>and</strong> authority’s requirement<br />
Siting of generator set room <strong>and</strong> layout of generator set are important as they affect the<br />
performance of the equipment. Generator set room should have as many external walls as possible.<br />
In any case it is not advisable to have less than 2 external walls.<br />
The minimum clearance height of the generator set room should be given careful consideration<br />
during planning stage. If the minimum clearance height is insufficient, the exhaust system may not<br />
be able to be properly installed resulting in high back pressure. This affects the performance of the<br />
generator set <strong>and</strong> increases the noise level as well.<br />
March 2009 7-11