31.12.2014 Views

Volume 8 – Mechanical and Electrical Services - Malaysia Geoportal

Volume 8 – Mechanical and Electrical Services - Malaysia Geoportal

Volume 8 – Mechanical and Electrical Services - Malaysia Geoportal

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Chapter 7 ELECTRICAL SERVICES<br />

7.3.5.2 Switchgears<br />

The switchgears normally encountered are the ordinary lamp <strong>and</strong> socket outlet switches, isolators<br />

fuse switches, switchfuse, circuit breakers, changeover switches <strong>and</strong> contactors.<br />

Given below are some useful notes on the more commonly used protective <strong>and</strong> isolating devices.<br />

a) Isolators - These are used for local isolation only. They are not used for<br />

cable protection.<br />

b) Switch fuse/ switch fuse- This is a single unit made up of an isolator in series with an<br />

HRC fuse the HRC Fuse being retractable. It comes in both<br />

SP & N <strong>and</strong> TP & N configurations with st<strong>and</strong>ard rating being<br />

20A, 30A, 45A <strong>and</strong> 60A.<br />

c) MCCB This is both an isolating as well as a protective device to<br />

control loads above 100A to 400A<br />

d) Air-circuit-breakers - These together with over-current <strong>and</strong> earth leakage relays<br />

are used for busbar ratings of 400A <strong>and</strong> above. They are<br />

expensive but efficient tripping devices.<br />

MCBs <strong>and</strong> MCCBs are generally being introduced to replace h.r.c.fuses, switch fuses, <strong>and</strong> even air<br />

circuit breakers on account of their compact size, ease of maintenance <strong>and</strong> neat appearance when<br />

incorporated into cubicles.<br />

The choice of circuit breaker must conform to the fault level designed for. The interrupting capacity<br />

of the circuit breaker must be equal to or greater than the amount of fault current that can be<br />

delivered at the point in the system where the breaker is applied. The amount of fault current<br />

supplied by a system can be calculated at any point in the system.<br />

The following interrupting capacities should be considered for the 240/415V system:-<br />

Main Switch Board : 43 KA(31MVA) to 32 KA(23MVA)<br />

SUB Switch Board : 22KA 916MVA) to 14 KA(10MVA)<br />

Distribution Board : 10KA to 6 KA<br />

7.3.6 Distribution Board<br />

Distribution board normally is wall mounted type. It consists of isolating switchgears, final sub circuit<br />

breakers for over current <strong>and</strong> earth leakage protection. The mounting height for a distribution board<br />

shall be 2m measured from the floor to the underside of the distribution board.<br />

7.3.7 Generator Set<br />

7.3.7.1 Generator room selection <strong>and</strong> authority’s requirement<br />

Siting of generator set room <strong>and</strong> layout of generator set are important as they affect the<br />

performance of the equipment. Generator set room should have as many external walls as possible.<br />

In any case it is not advisable to have less than 2 external walls.<br />

The minimum clearance height of the generator set room should be given careful consideration<br />

during planning stage. If the minimum clearance height is insufficient, the exhaust system may not<br />

be able to be properly installed resulting in high back pressure. This affects the performance of the<br />

generator set <strong>and</strong> increases the noise level as well.<br />

March 2009 7-11

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!