Chapter 7 ELECTRICAL SERVICES<br />

Table 7.1 NEMA Code for Start kVA/HP for 3-phase Squirrel Cage Motors<br />

Remarks : If Start kVA is not known, use the higher value.<br />

Code StartkVA/HP Mostly Used On<br />

A 0 <strong>–</strong> 3.15<br />

B 3.15 <strong>–</strong> 3.55 Normal Torque, Low Starting Current<br />

C 3.55 <strong>–</strong> 4.00 High Torque, Low Starting Current<br />

D 4.00 <strong>–</strong> 4.50 High Torque, High Slip<br />

E 4.50 <strong>–</strong> 5.0<br />

F 5.0 <strong>–</strong> 5.6 >15 Hp<br />

G 5.6 <strong>–</strong> 6.3 10Hp<br />

H 6.3 <strong>–</strong> 7.1 < 7.5 HP but > 5 HP<br />

J 7.1 <strong>–</strong> 8.0 3 HP<br />

K 8.0 <strong>–</strong> 9.0 > 1.5 HP but < 2 HP<br />

L 9.0 <strong>–</strong> 10.0 1 HP<br />

M 10.0 <strong>–</strong> 11.2 < 1HP<br />

etc<br />

Table 7.2 Reduced Voltage Assistance Starting from NEMA Code<br />

Code Starting Method Starting kVA (%) Starting Torque (%)<br />

C Reactor or Resistance 80% Tap 80 64<br />

D Start - Delta 33 33<br />

E Half Winding 65 50<br />

The calculation shall be based on NEMA st<strong>and</strong>ard for estimating the starting KVA for the water pump<br />

motor. Sample of calculation shall be tabled in Appendix 7E<br />

7.3.7.3 Maintenance<br />

Maintenance can be divided into:-<br />

a) Correction maintenance<br />

- All maintenance performed in order to correct to failure<br />

b) Preventive maintenance<br />

- Direct preventive maintenance performed in order to prevent failure from accuring (eg.<br />

Cleaning lubrication at regular intervals).<br />

- Indirect Preventive maintenance or condition monitoring are all measures taken to discover<br />

faults before they result in operational disturbances or unnecessary damage (eg.<br />

Performance monitoring <strong>and</strong> testing)<br />