Chapter 7 ELECTRICAL SERVICES<br />

APPENDIX 7G SAMPLE INSPECTION FORMAT FOR GENERATOR SET<br />

GENERATOR SET INSPECTION CHECK LIST<br />

TITLE OF PROJECT:<br />

ITEM DESCRIPTION CONDITION REMARK<br />

A<br />

Generator Room<br />

A.1 Clean the generator room<br />

A.2 Record all generator set parameters into the log book<br />

B<br />

Lubricating System<br />

B.1 Check lubricating oil level, replenish if necessary<br />

B.2<br />

B.3<br />

B.4<br />

Change lubricating oil filters half-yearly or 250 hours<br />

whichever<br />

occurs first.<br />

Check hydraulic governor oil level, replenish if<br />

necessary<br />

Check hydraulic governor oil at 12 th month or 1500<br />

hrs whichever<br />

occurs first.<br />

B.5 Visual inspection for indication of unusual conditions.<br />

C<br />

Fuel System<br />

C.1 Check operation of fuel transfer pumps.<br />

C.2<br />

Change fuel filters half-yearly or 250 hours whichever<br />

occurs first.<br />

C.3 Visual inspection for indication of fuel leaks.<br />

C.4 Check <strong>and</strong> clean air intake filters<br />

C.5 Change air intake filters<br />

D<br />

Cooling System<br />

D.1 Check coolant level, replenish if necessary.<br />

D.2 Check condition of hose <strong>and</strong> connections<br />