Chapter 10 SCADA AND AUTOMATION SYSTEM<br />
The system shall build in 2 control profiles for installed system namely Irrigation mode <strong>and</strong> Drainage<br />
mode. In drainage mode, the system will drain out the water automatically as the tide low, <strong>and</strong> close<br />
the gate as the tide going high. In irrigation mode, the system will reserve the water at setting level<br />
for irrigation level <strong>and</strong> drain out the water as the level achieve the setting level during tide low. The<br />
system shall close the gate as the tide up or the water level achieves irrigation low level.<br />
These two modes of control operation are totally contrary to one another. If one sets the control to<br />
irrigation mode, the control system keeps the water. But if one sets the control to drainage mode,<br />
the control will flushes the water instead. A good Watergate system must able to h<strong>and</strong>le both of<br />
these controls in the same system. Thus, the consultant team proposed that the system should build<br />
in both of these two modes for users convenient. Users only need to change the setting on the<br />
control panel <strong>and</strong> the system will start to perform that particular mode of control without any<br />
modification or changes in the system. This is what so call user friendly Watergate control system.<br />
10.5.2 Automatic Control mode<br />
The system shall be able to detect the high tide <strong>and</strong> low tide <strong>and</strong> prevent the sea water to flow into<br />
river. However, the system shall intelligent enough to open the gate as upstream level is higher than<br />
downstream during high tide <strong>and</strong> at the same time prevent the sea water to flow into the river.<br />
Control algorithm of automatic control shall be intelligent enough to make accurate decision on gate<br />
control. Gate shall not open <strong>and</strong> close too frequent to avoid actuator from burn out. The system shall<br />
be intelligent enough to take accurate tide level <strong>and</strong> not affected by any interference like boat’s<br />
wave.<br />
10.5.3 Remote Control <strong>and</strong> Remote Monitoring Mode<br />
The system shall able to provide remote control mode with password protected. Users shall be able<br />
to login to system remotely at any moment <strong>and</strong> any location using any notebook or any PC without<br />
any special software to do remote monitoring <strong>and</strong> remote control as long as users have username<br />
<strong>and</strong> password to do so. (For remote control, multi layer password shall be applied for security<br />
purposes). User shall be allowed to access remote control mode from MMI through web server OR<br />
directly from RTU web SCADA.<br />
10.5.4 Manual Push Button Control Mode<br />
The system shall provide manual control mode where users can only control the gate at site by<br />
pressing open or close button at the panel. Manual control mode shall have higher priority than auto<br />
<strong>and</strong> remote control for security purposes especially during maintenance.<br />
10.5.5 Local Control Mode<br />
The system shall provide local control at actuator <strong>and</strong> local gear box. There are two local control<br />
modes available for the system includes:<br />
a) Local actuator control mode whereby operator may lift up the gate by select the<br />
actuator to actuator local control mode at actuator <strong>and</strong> push on open button to open<br />
<strong>and</strong> close button to close the gate. Operator may also push on stop button to stop<br />
the operation of the actuator.<br />
b) Local Manual Control mode whereby operator may open or close the gate by turn on<br />
manually on the h<strong>and</strong>wheel provided at actuator or gear box.<br />
10-16 March 2009