Chapter 10 SCADA AND AUTOMATION SYSTEM<br />

The system shall build in 2 control profiles for installed system namely Irrigation mode <strong>and</strong> Drainage<br />

mode. In drainage mode, the system will drain out the water automatically as the tide low, <strong>and</strong> close<br />

the gate as the tide going high. In irrigation mode, the system will reserve the water at setting level<br />

for irrigation level <strong>and</strong> drain out the water as the level achieve the setting level during tide low. The<br />

system shall close the gate as the tide up or the water level achieves irrigation low level.<br />

These two modes of control operation are totally contrary to one another. If one sets the control to<br />

irrigation mode, the control system keeps the water. But if one sets the control to drainage mode,<br />

the control will flushes the water instead. A good Watergate system must able to h<strong>and</strong>le both of<br />

these controls in the same system. Thus, the consultant team proposed that the system should build<br />

in both of these two modes for users convenient. Users only need to change the setting on the<br />

control panel <strong>and</strong> the system will start to perform that particular mode of control without any<br />

modification or changes in the system. This is what so call user friendly Watergate control system.<br />

10.5.2 Automatic Control mode<br />

The system shall be able to detect the high tide <strong>and</strong> low tide <strong>and</strong> prevent the sea water to flow into<br />

river. However, the system shall intelligent enough to open the gate as upstream level is higher than<br />

downstream during high tide <strong>and</strong> at the same time prevent the sea water to flow into the river.<br />

Control algorithm of automatic control shall be intelligent enough to make accurate decision on gate<br />

control. Gate shall not open <strong>and</strong> close too frequent to avoid actuator from burn out. The system shall<br />

be intelligent enough to take accurate tide level <strong>and</strong> not affected by any interference like boat’s<br />

wave.<br />

10.5.3 Remote Control <strong>and</strong> Remote Monitoring Mode<br />

The system shall able to provide remote control mode with password protected. Users shall be able<br />

to login to system remotely at any moment <strong>and</strong> any location using any notebook or any PC without<br />

any special software to do remote monitoring <strong>and</strong> remote control as long as users have username<br />

<strong>and</strong> password to do so. (For remote control, multi layer password shall be applied for security<br />

purposes). User shall be allowed to access remote control mode from MMI through web server OR<br />

directly from RTU web SCADA.<br />

10.5.4 Manual Push Button Control Mode<br />

The system shall provide manual control mode where users can only control the gate at site by<br />

pressing open or close button at the panel. Manual control mode shall have higher priority than auto<br />

<strong>and</strong> remote control for security purposes especially during maintenance.<br />

10.5.5 Local Control Mode<br />

The system shall provide local control at actuator <strong>and</strong> local gear box. There are two local control<br />

modes available for the system includes:<br />

a) Local actuator control mode whereby operator may lift up the gate by select the<br />

actuator to actuator local control mode at actuator <strong>and</strong> push on open button to open<br />

<strong>and</strong> close button to close the gate. Operator may also push on stop button to stop<br />

the operation of the actuator.<br />

b) Local Manual Control mode whereby operator may open or close the gate by turn on<br />

manually on the h<strong>and</strong>wheel provided at actuator or gear box.<br />

10-16 March 2009