Installation<br />

Table 3–5. AC Microchron II Timer Relay Installation Procedure (Cont.)<br />

Step<br />

Procedure<br />

8 When setting the time, use the standard representation.<br />

Tens<br />

Minutes<br />

Unit<br />

Minutes<br />

Tens<br />

Seconds<br />

Unit<br />

Seconds<br />

Tenth of<br />

Seconds<br />

1 9 5 9 9<br />

This example shows a setting of 19 minutes and 59.9 seconds. A time set at<br />

89.9 seconds would read 01:29.9.<br />

9 Energize the timer and verify the elapsed time with an external timing device<br />

from the instant energy is applied until the relay front contacts close.<br />

A red LED illuminates when power is first applied; it blinks until the delay set on<br />

the switches has expired.<br />

Then, a green LED illuminates to indicate that the delay has expired.<br />

The operational relay timing must be within ±0.1% of the time pre-selected by<br />

the thumbwheel switches plus a maximum delay of 0.75 seconds.<br />

If the timing is not within acceptable limits, remove and replace the relay.<br />

Then perform the mechanical and electrical tests provided in Section 6,<br />

Corrective Maintenance, on the malfunctioning relay.<br />

10 Reseal access to the thumbwheel switches by sliding the clear plastic cover<br />

over the two studs and securing it in place with the two thumbnuts. Install a new<br />

tamper evident lead seal (P/N 35285-000-00), using the holes in the studs, and<br />

crimp securely.<br />

11 Verify the time setting.<br />

P1457, Rev. Nov/07 3–15 <strong>Alstom</strong> Signaling Inc.