Preventive Maintenance<br />

4.5.2. AC Vane Relay Test<br />

To test a two-element vane relay follow the procedure provided in Table 4–8. To<br />

operate the text fixture see Appendix C.<br />

Table 4–8. AC Vane Relay Test Procedure<br />

Step<br />

Procedure<br />

1 Perform the visual inspection procedure in Table 4–3.<br />

2 Connect the relay, meters and transformer, if required, to the Vane Relay Test<br />

Unit.<br />

LINE<br />

EARTH<br />

NEUTRAL<br />

POWER<br />

12 11<br />

SW1<br />

FUSE<br />

2A<br />

TP1<br />

SW2<br />

12<br />

11<br />

LINE/TRACK<br />

POWER<br />

Rs<br />

FINE<br />

100 OHMS<br />

AC SUPPLY LINE<br />

SW-1<br />

POWER<br />

ON<br />

LINE/TRACK<br />

POWER<br />

Rp<br />

COURSE<br />

250 OHMS<br />

R1<br />

50 OHMS<br />

22<br />

21 SHUNT<br />

12 11<br />

SW3<br />

SHUNT<br />

11 12<br />

SW4<br />

CURRENT<br />

VOLTS<br />

COIL<br />

2 ELEMENT VANE RELAY<br />

COIL<br />

VOLTS<br />

CURRENT<br />

– + + – – + + – – + + -<br />

AMMETER<br />

0-250 mA<br />

VOLTMETER<br />

0-150 VOLTS<br />

11<br />

14<br />

12<br />

13<br />

LOCAL<br />

R<br />

TRACK<br />

61<br />

64<br />

62<br />

63<br />

VOLTMETER<br />

0-150 VOLTS<br />

AMMETER<br />

0-2 AMPS<br />

LOCAL<br />

TRACK<br />

3 Carefully adjust supply voltage (a tapped transformer is one means) so that the<br />

local element of the relay has the rated voltage imposed.<br />

Stabilize relay for at least one hour before taking electrical values with nominal<br />

voltage on the local element.<br />

Make allowance for the voltage drop across the milliammeter. Obtain local<br />

element readings.<br />

4 Shunt the local milliammeter and adjust the local element voltage so that the<br />

rated voltage is impressed. Hold this value constant during test.<br />

5 No voltmeter is required for the track element, as DROPAWAY, DROPAWAY to<br />

stop, PICKUP, and WORKING are expressed in current values.<br />

6 While holding the voltage on the local element constant at its rated value and<br />

with the relay in its normal position, vary the track element current by moving<br />

the slider on the potentiometer or adjustable resistor. Determine the<br />

DROPAWAY, DROPAWAY to stop, PICKUP, and WORKING current values for<br />

the track element.<br />

P1457, Rev. Nov/07 4–12 <strong>Alstom</strong> Signaling Inc.