Corrective Maintenance<br />

6.5.2. Mechanical Test and Adjustment Procedure<br />

The Mechanical Test and Adjustment Procedure provided in Table 6–11 applies to<br />

standard B1 and B2 relays, not specialty relays.<br />

Table 6–11. Mechanical Test and Adjustment Procedure<br />

Step<br />

Procedure<br />

1 Inspect the relay components by following the procedure in Tables 6–10.<br />

NOTE<br />

If the relay is a Microchron II Timer Relay (AC or DC), first remove<br />

the timer using the procedure provided in Table 6–12.<br />

2 Mount the relay onto Shop Test Rack or on a plugboard, supporting it about 18<br />

inches above a bench on a plugboard holding stand.<br />

Secure the relay with two retaining nuts to hold the relay in place.<br />

Example Shop Test Rack<br />

G<br />

16 26 36<br />

15 25 35<br />

14 24 34<br />

13 23 33<br />

12 22 32<br />

11 21 31<br />

46 56 66<br />

45 55 65<br />

44 54 64<br />

43 53 63<br />

42 52 62<br />

41 51 61<br />

E<br />

F<br />

6C<br />

6D<br />

D<br />

C<br />

1C<br />

1D<br />

6C<br />

6D<br />

C<br />

D<br />

A<br />

B<br />

X<br />

This rack is designed for both B1 and B2 relays. One of the guide rods is<br />

removable. For testing B1 relays, screw the removable guide rod into location F.<br />

For testing B2 relays, screw it into location E. Meter leads should have alligator<br />

clips for clipping on to terminal posts G.<br />

3 Proceed with this procedure to check the following areas to verify that all<br />

adjustments are proper: armature air gap, bridge travel, back and front contact<br />

make and break, contact openings and pressures.<br />

4 Energize the relay when required. To power the relay, apply a variable current<br />

source to the coil leads (one coming from each relay coil), utilizing a meter tip<br />

plug to interface the current source with the female cap connectors on the coil<br />

leads. Refer to the relay wiring diagram if necessary.<br />

P1457, Rev. Nov/07 6–17 <strong>Alstom</strong> Signaling Inc.