Preventive Maintenance<br />

4.5.4. Code-Responsive Relay Test<br />

To obtain operating values for the code-responsive relay follow the procedure in<br />

Table 4–10.<br />

Table 4–10. Code-Responsive Relay Test Procedure<br />

Step<br />

Procedure<br />

1 Perform the visual inspection procedure in Table 4–5.<br />

2 Saturate relay coils at current value specified on specific ED sheet.<br />

3 Operate relay several times by opening and closing circuit.<br />

4 Slowly reduce current to obtain DROPAWAY value. Two readings of<br />

DROPAWAY values should be taken, one to close back contacts and the other<br />

to allow the armature to touch its backstop pin.<br />

5 Open the circuit, close the circuit, and then slowly increase the current to obtain<br />

PICKUP and WORKING values. PICKUP is the current value at which the front<br />

contacts just close. WORKING is the current value at which the armature in the<br />

fully energized position is up against the stop.<br />

P1457, Rev. Nov/07 4–14 <strong>Alstom</strong> Signaling Inc.