Installation<br />

Table 3–3. Microchron II Timer Relay (DC) Installation Procedure (Cont.)<br />

Step<br />

Procedure<br />

10 When setting the time, use the standard representation.<br />

Tens<br />

Minutes<br />

Unit<br />

Minutes<br />

Tens<br />

Seconds<br />

Unit<br />

Seconds<br />

1 9 5 9<br />

This example shows a setting of 19 minutes and 59 seconds. A time set at 89<br />

seconds would read 01:29.<br />

11 Energize the timer and verify the elapsed time with an external timing device<br />

from the instant energy is applied until the relay front contacts close.<br />

The operational relay timing must be within ±0.1% of the time pre-selected by<br />

the thumbwheel switches plus a maximum delay of 0.75 seconds.<br />

If the timing is not within acceptable limits, remove and replace the relay.<br />

Then perform the mechanical and electrical tests provided in Section 6,<br />

Corrective Maintenance, on the malfunctioning relay.<br />

12 For timers with a tamper evident color seal (see figure in Step 8), replace the<br />

plastic seal. For relays with a tamper evident lead seal (P/N 35285-000-00),<br />

replace switch cover, thumbnuts, seal, and crimp seal.<br />

13 Verify the time setting.<br />

P1457, Rev. Nov/07 3–11 <strong>Alstom</strong> Signaling Inc.