Preventive Maintenance<br />

4.5.11. Switch-Overload Relay Test<br />

The switch-overload relay requires special adjustment. See specific ED sheet for exact<br />

details and operating values.<br />

Table 4–17. Switch-Overload Relay Test Procedure<br />

Step<br />

Procedure<br />

1 Perform the visual inspection procedure in Table 4–2.<br />

2 See specific ED sheet for specifications.<br />

3 Apply the minimum specified operating current to the terminals of the pick up<br />

winding (low resistance) with positive energy on 3C and negative energy on 3D.<br />

After 1½ minutes back off overpressure spring until relay picks. Lock spring at<br />

this setting.<br />

4 Allow relay to cool at least 10 minutes.<br />

5 Apply the minimum specified operating current to the terminals of the pick up<br />

winding for 1½ minutes. Relay must not pick. After 1½ minutes, quickly increase<br />

current to maximum pick up current. Relay must pick up. Remove power.<br />

6 Check high resistance winding to insure the PICKUP and WORKING current<br />

value is within specified limits.<br />

P1457, Rev. Nov/07 4–21 <strong>Alstom</strong> Signaling Inc.