THERM<br />
Indicates the state of the motor thermostat input.<br />
0 = thermostat input closed (normal)<br />
1 = thermostat input open (overheat condition)<br />
Firmware Versions: 3.1.0 <strong>and</strong> later Type: switch (R) Units: N/A<br />
Range: 0, 1 Default: hardware defined EEPROM: No<br />
Opmodes: All Drive Status: EN/DIS<br />
THERMODE<br />
Determines the operation of the drive when the Motor Thermostat Input (THERM) opens.<br />
0 = disable drive <strong>and</strong> open fault relay immediately<br />
1 = disable drive after 2 minutes; open fault relay immediately<br />
2 = do not disable drive; open fault relay immediately<br />
3 = ignore thermostat input<br />
4 = issue warning; no other action*<br />
5 = issue warning, open fault relay after THERMTIME elapses*<br />
* Firmware versions 3.1.0 <strong>and</strong> later<br />
Opening the fault relay sets RELAY=0.<br />
Firmware Versions: All Type: switch mode (R/W) Units: N/A<br />
Range: 0 to 5 Default: 0 EEPROM: Yes<br />
Opmodes: All Drive Status: EN/DIS<br />
THERMTIME<br />
Sets the number of seconds the drive waits after motor over-temperature detection before it opens the fault relay<br />
(THERMODE = 5 only).<br />
Firmware Versions: 3.1.0 <strong>and</strong> later Type: variable (R/W) Units: seconds<br />
Range: 1 to 300 Default: 30 EEPROM: Yes<br />
Opmodes: All Drive Status: EN/DIS<br />
THERMTYPE<br />
Sets the motor temperature sensor type:<br />
0 = PTC (Positive Temperature Coefficient)<br />
1 = NTC (Negative Temperature Coefficient)<br />
Firmware Versions: 3.1.0 <strong>and</strong> later Type: switch (R/W) Units: seconds<br />
Range: 0, 1 Default: 0 EEPROM: Yes<br />
Opmodes: All Drive Status: EN/DIS<br />
TRUN<br />
Provides a relative incremental run time counter. Error log stamps include the value of this counter at the time<br />
of the error. The clock is a very coarse counter <strong>and</strong> is incremented every 15 minutes. It is intended for use by<br />
factory Quality Assurance Program personnel. This clock has a resolution of 15 minutes <strong>and</strong> is reset only when<br />
the CLREEPROM comm<strong>and</strong> is used.<br />
Firmware Versions: All Type: variable (R) Units: hours: minutes<br />
Range:0000:00 to 9999:45 Default: N/A EEPROM: Yes<br />
Opmodes: All Drive Status: EN/DIS<br />
91