28.11.2012 Views

Setup and Reference Guide - Kollmorgen

Setup and Reference Guide - Kollmorgen

Setup and Reference Guide - Kollmorgen

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

DISTIME<br />

Sets the amount of time to wait after motor speed goes below DISSPEED before the drive is disabled in the<br />

Active Disable process. Once motor speed goes below DISSPEED, the drive waits for the time period specified<br />

by DISTIME, <strong>and</strong> then disables the drive. See also ACTFAULT, DECSTOP, DISSPEED, <strong>and</strong> O1MODE=5.<br />

Firmware Versions: 2.1.0 <strong>and</strong> later Type: variable (R/W) Units: millisecond * 0.1<br />

Range: 0 to 65535 Default: 100 EEPROM: Yes<br />

Opmodes: All Drive Status: EN/DIS<br />

DIVISIONS<br />

Sets the number of divisions used for indexing (divides PROTARY).<br />

Only used when MODMODE = 1<br />

Firmware Versions: 3.7.0 <strong>and</strong> later<br />

Default: 4<br />

Range: 2 to 32767<br />

-2 to -32767<br />

31<br />

EEPROM: Yes<br />

DRIVEOK<br />

Displays the status of the drive faults.<br />

0 = faults exist<br />

1 = no faults exist<br />

Firmware Versions: All Type: switch (R/W) Units: N/A<br />

Range: 0, 1 Default: N/A EEPROM: No<br />

Opmodes: All Drive Status: EN/DIS<br />

DUMP<br />

Transmits all variables <strong>and</strong> their settings to the serial port terminal. This comm<strong>and</strong> actually outputs the<br />

EEPROM contents of the drive to the serial port, where the variables can then be reviewed or saved to a variable<br />

file (*.SSV).<br />

Firmware Versions: All Comm<strong>and</strong> Syntax: DUMP<br />

Opmodes: All Drive Status: EN/DIS<br />

DUALFB<br />

Enables/disables the reading of an external feedback signal through the C8 connector.<br />

0 = no dual loop<br />

1 = dual loop without checking for external feedback fault<br />

2 = dual loop with checking for external feedback fault<br />

The fault options above can relate to a line break; however, the motor must be in<br />

motion for this detection to occur. It can also indicate a wrong XENDIR<br />

parameter.<br />

Firmware Versions: 3.3 <strong>and</strong> later Type: switch (R/W) Units: N/A<br />

Range: 0, 1, 2 Default: 0 EEPROM: Yes<br />

Opmodes: 8 Drive Status: DIS